Paint Drying Oven Classified as Hazardous Material Drying Equipment
DRY TEC Complies with Hazardous Material Drying Equipment Regulations
Therefore, its installation requires notification to the local fire department.
Takubo Engineering's paint drying oven "DRY TEC" meets the requirements for hazardous material drying equipment:
- Indirect heating method: Ensures ignition sources do not enter the oven.
- Air exchange: Maintains hazardous material concentration below 50% of the lower explosive limit by exchanging 5m³/m of air inside the furnace.
- Additionally, various safety devices such as monitoring systems, pre-purge and post-purge functions, and optional explosion relief vents are implemented.